EasyManua.ls Logo

Midea VC Pro Series

Midea VC Pro Series
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VC Pro VRF 50/60Hz
28
60-66HP
Table 2-1.9: 60-66HP specifications
HP
60
62
64
66
Model name
MVC-1700WV2GN1
MVC-1750WV2GN1
MVC-1795WV2GN1
MVC-1850WV2GN1
Combination type
30HP+30HP
30HP+16HP+16HP
26HP+22HP+16HP
28HP+22HP+16HP
Power supply
V/Ph/Hz
380-415V 3N~50/60HZ
Cooling
1
Capacity
kW
170.0
175.0
179.5
185.0
kBtu/h
580.6
597.8
613.0
631.8
Power input
kW
59.02
54.03
55.89
58.57
EER
2.88
3.24
3.21
3.16
Connected
indoor unit
Total capacity
50-130%
Maximum quantity
64
Compressor
Type
DC inverter
Quantity
4
5
Oil type
FV 50s
Start-up method
Soft start
Fan
Type
DC
Quantity
4
5
Motor output
kW
0.56×4
0.56×2+0.75×2
0.56×4+0.75
Static pressure
Pa
20 default;60 customization option
Airflow rate
m3/h
41200
43800
43400
44400
Drive type
20 default;60 customization option
Refrigerant
Type
R410A
Factory charge
kg
19×2
19+11×2
19+13+11
Pipe
connections
2
Liquid pipe
mm
19.1
Gas pipe
mm
41.2
Sound pressure level
3
dB(A)
66
Net dimensions (W×H×D)
mm
(1585×1615×765)×2
(1585×1615×765)+
(960×1615×765)×2
(1585×1615×765)+(1250×1615×765)+(960
×1615×765)
Packed dimensions (W×H×D)
mm
(1650×1810×840)×2
(1650×1810×840)+
(1025×1790×830)×2
(1650×1810×840)+(1305×1790×820)+(102
5×1790×830)
Net weight
kg
338×2
338+197×2
338+278+197
Gross weight
kg
362×2
362+213×2
362+297+213
Ambient temp.
Cooling
o
C
-5 to 55
Notes:
1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those of the unit's accessories.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

Related product manuals