16
Main Menu (menu icon)
BATTERY SETUP (menu icon)
NEW (TEST) (icon)
(Continued from REFERENCE)
STRING INFO (scrolling parameters list)
VOLT & CONDUCTANCE (default)
Press
ENTER to measure volts only; volts and conductance si-
multaneously; or voltage rst, then conductance.
MODE (check boxes)
VOLTAGE ONLY
VOLT & CONDUCTANCE
VOLTS THEN CONDUCT(ANCE)
TEMPERATURE
Press
ENTER to select the units of measure and the temperature
of the string. Conductance measurements change with jar tem-
perature. To compensate, the ULTRA uses the temperature you
select to adjust the percentage of the reference value.
TEMP. UNITS (check boxes)
DEGREES F
DEGREES C
TEMPERATURE (scrolling/numeric)
Range: 0 to 50 °C ( 32 to 122 °F).
AC RIPPLE
Press
ENTER to select the string’s AC ripple.
AC RIPPLE (scrolling/numeric)
Select from 0.000 to 99.999 volts.
DC FLOAT V.
Press
ENTER to select the string’s DC oat voltage.
DC FLOAT (scrolling/numeric)
Select from 0.00 to 600.00 volts.
(To DC FLOAT A.)
Main Menu
BATTERY SETUP MENU
Chapter 2: Description Celltron ULTRA