Connect the control and safety devices in compliance with the previously
mentioned electrical installation standards.
The main automation components are:
Control panel and incorporated receiver Pair of outside photocells
Key selector Pair of inside photocells
Blinker tuned in with antenna
1-2-4 channel transmitter
Operator Antenna cable
Warning! For actuator wiring and accessory connection, refer to the relevant
instruction manuals. The control panels and accessories must be suitable for use
and conform to current standards.
Should the opening or closing direction be incorrect, it is possible to invert the
connections of operation 1 and operation 2 on the control board.
The first command after an interruption of the power supply should be an
opening maneuver.
7. CHECKING THE AUTOMATION
Before considering the automation completely operational, the following checks
must be made with great care:
• Check that all the components are firmly anchored.
• Control all the safeties work properly (i.e. photocells, pneumatic skirt, etc.).
• Check the emergency maneuvers control.
• Check the opening and closing maneuvers using the controls.
• Check the control unit’s electronic logic in normal (or customized) operation.
8. USE OF THE AUTOMATION
Since the automation may be remote controlled either by radio or a Start button, it
is essential that all safeties are checked frequently.