13
115 (230) VAC
50 or 60 Hz, +/-0 Hz, unless synchronized to utility during brownout
Simulate sine-wave
Overcurrent and short circuit protected, latching shutdown on overload
8
SPECIFICATIONS
3 to 6 years, depending on the number of discharge cycles and ambient temp.
2 to 5 hours from total discharge
<5%
<1%
0 - 160 (0 - 282) VAC
85 - 152 (170 - 285) VAC
105 - 136 (210 - 250) VAC
50 or 60 Hz, autosensing
Resettable circuit breaker
50 or 60 Hz, +/-5%
2 - 4 ms typical
320VA
208W
520VA
338W
700VA
455W
1000VA
670W
1400VA
950W
500 J (440J)
19.5 kAmps total
500 J (440J)
39 kAmps total
0 ns (instantaneous) normal mode; <5 ns common mode
<5%
<0.5%
NOTE: 230VAC Specs Shown In ( ) 320VA 520VA 700VA 1000VA 1400VA
17.8 (19.2)
Kg
39.3 (42.4)
Lb
0 to 40 degrees C (+32 to 104 degrees F)
-15 to +45 degrees C (+5 to +113 degrees F)
0 to 95%, non-condensing
0 to +3,000 m (0 to + 10,000 ft)
0 to +15,000 m (0 to +50,000 ft)
IEC 801-2 level IV, 801-4 level IV, 801 -5 level III
<45 dBA
22.2 x 22.8 x 21.6 cm
(8.65 x 9.0 x 8.5 in)
30.5 x 31.1 x 28.6 cm
(12.0 x 12.25 x
11.25 in)
10.2 (11.2)
Kg
22.4
(24.7) Lb
24.4 (25.8
Kg
53.7
(56.8) Lb
7.5 (8.4) Kg
16.4 (18.6)
Lb
Listed to UL 1778 Compliance to CSA 22.2
Acceptable input voltage
Input voltage (on-line operation)
Output voltage
Nominal input frequency
Input protection
Frequency limits (on-line operation)
Transfer time
Maximum load
On-battery output voltage
On-battery frequency
On-battery waveshape
Protection
Surge energy rating
(one time, 10/1000 us waveform)
Surge current capability
(one time, 8/20 us waveform)
Surge response time
Surge voltage let-through
(percentage of applied ANSI
C62.41 Cat. A +/-6 V test waveform)
Noise filter
Battery Type-Spill proof, maintenance free,
user replaceable, sealed lead-acid
Typical battery life
Typical recharge time
Operating temperature
Storage temperature (see Section 11)
Operating and storage relative humidity
Operating elevation
Storage elevation
Electromagnetic immunity
Audible noise at 1 m (3 ft.)
Size (H x W x D)
Weight - Net (Shipping)
Normal and common mode EMI/RFI suppression
one 12v, 7 Ah
one 12v, 11
Ah
10 Base-T surge protection
let-through (as a percentage of an
applied +/-6 kV 1.2/50 us, 500
a 8/20 us test)
Telephone line surge protection let-through
(as a percentage of an applied +/-6 kV 1.2/50
us, 500 a 8/20 us test
6.9 (8) Kg
15.4 (17.6)
Lb
Safety and approvals
EMC Verification
FCC Class B certified
two 12v
17 Ah
two 12v
11 Ah
English