EasyManuals Logo

Minuteman SNMP-NV6 User Manual

Minuteman SNMP-NV6
43 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
SNMP-NV6
Page 19
5.3.1.1 Auto Restart
Sends the command to the UPS to configure the auto restart function.
5.3.1.2 UPS Buzzer
Sends the command to the UPS to configure the buzzer function.
5.3.1.3 Low Battery
The set value is compared to the received value from the UPS. If the received battery
level is lower than the assigned value then the card sends the Low Battery Warning.
5.3.1.4 UPS Shutdown Action
The set value is compared to the received value from the UPS. If the Power Fail or Low
Battery event occurs then the card sends the assigned shutdown delay time to the UPS.
5.3.1.5 Smart Shutdown
Initiates a signal for the server to shutdown. After the user-defined Estimated OS
Shutdown Delay, the output power is switched off. SNMP-NV6 Client or SNMP
Shutdown Agent must be used on the server for it to be properly shutdown. The
Estimated OS Shutdown Delay includes the assigned countdown delay in the shutdown
software plus the duration of OS shutdown process. When the Shutdown Agent receives
the Smart Shutdown signal, the low battery settings will be used to process the shutdown
procedure.
5.3.1.6 Battery Replacement Date
After the battery replacement dates are assigned, the card then sends the command to
store these dates in the UPS.
5.3.1.7 External Battery Pack
If you are using an External Battery Pack with this UPS, the UPS must be configured so
that; the UPS will report the correct estimated runtime.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Minuteman SNMP-NV6 and is the answer not in the manual?

Minuteman SNMP-NV6 Specifications

General IconGeneral
BrandMinuteman
ModelSNMP-NV6
CategoryMeasuring Instruments
LanguageEnglish