37.1 ULI/ULC Integrated Fire Alarm and Audio Panel Specifications
37.1.1 PS-2040 Power Supply
• 0 to 49 degrees Celsius, 0 to 93 + or - 2% RH (non-condensing) operating range
• Power input: 120 VAC, 60Hz, 12A or 240 VAC, 50Hz, 6A (primary), Not Power-limited
• Power supply ratings: 8.5A (x2), 18.85-0-18.85V (secondary)13A, 29V (secondary)
37.1.2 Model QPS-5000N & QBC-5000N Power Supply & Charger
• Primary input 120 VAC, 60Hz, or 240 VAC, 50HZ, 12Amp, Not Power-limited
• Charging for up to 65 AH of 24 VDC batteries
• Float Type Charger
37.1.3 Model FNC-2000 Fire Network Controller Module
• Current consumption: standby: 190mA
alarm: 190mA
37.1.4 Model ANC-4000 Audio Network Controller Module
• Current consumption: standby: 255mA
alarm: 265mA
37.1.5 Model TNC-5000 Telephone Network Controller Module
• Current consumption: standby: 195mA
alarm: 215mA
37.1.6 Model FOM-2000-UM Fiber Optics Module
• Current consumption: standby: 15mA
alarm: 15mA
37.1.7 Model QAA-5160-70/25 Amplifier with one 70V or 25V, 60 Watt Zone
• 70.7Vrms or 25V constant voltage output
• One fully supervised Class "A" or "B" speaker Zone
• 60 watts per zone
• Freq. Response:
ULI bandwidth from 800 to 2800 Hz, ULC bandwidth from 400 to 4000 Hz
• Harmonic distortion less than 2.5% at 1 KHz
• Current consumption: standby: 55mA
alarm: 350mA, plus 65mA/Watt Speaker Power
37.1.8 Model QAA-5230-70/25 Amplifier with two 70V or 25V, 30 Watt Zones
• 70.7Vrms or 25V constant voltage output
• Two fully supervised Class "A" or "B" speaker zones
• 30 watts per zone
Note: All circuits are power limited, unless specified otherwise.