8.4 Two Stage Operation
In a two stage system, alarm inputs are either first stage (alert) inputs or second stage
(general alarm) inputs. First stage inputs include inputs from the following types of circuits:
non-verified alarm, verified alarm, sprinkler alarm, and water-flow alarm. Second stage inputs
include alarms on the general alarm circuits, activation of the General Alarm button, or
expiration of the Auto General Alarm timer. Any of these alarm inputs occurring when the
panel is not already in alarm cause the following:
The buzzer sounds steadily
If fire drill is active, it is cancelled
The Common Alarm LED turns on
The Common Alarm relay activates if Aux disconnect is not active
The Auto Signal Silence timer, if configured, starts
The Signal Silence Inhibit timer, if configured, starts
All Non-disconnected indicating programmed to the input are activated provided that
Aux disconnect is not active
If the alarm is a second stage alarm,
All non-disconnected strobe circuits are activated continuously
All non-disconnected signal circuits are activated at the evacuation rate
The General Alarm LED turns on.
If the alarm is a First Stage alarm,
Non-disconnected strobe circuits programmed to that circuit are activated continuously
Non-disconnected signal circuits programmed to that circuit are activated with the alert
code
The Auto General Alarm timer, if configured, starts
The General Alarm Cancel LED starts flashing.
Subsequent First Stage alarms when the panel is already in alarm, cause the following:
The buzzer sounds steadily
If signals have been silenced as a result of the silence button or the Auto signal silence
timer, signals are resounded as they were before signal silence, the Signal Silence LED
turns off, and the Auto Signal Silence timer, if configured, is restarted
If the panel is not already in General Alarm, additional non-disconnected signals
programmed to the new input are activated with the Alert Code (see Indicating (Signal)
Circuit Types sectionpage 76).
If the panel is not already in General Alarm and if the General Alarm Cancel LED is on
steady indicating that the Auto General Alarm timer has been Acknowledged the timer is
restarted and the General Alarm Cancel LED is extinguished.
A second stage alarm (general alarm) when the panel is already in alarm causes the following:
The buzzer sounds steadily
All non-disconnected signals are activated at the evacuation rate

Table of Contents

Other manuals for Mircom FleXNet FX-4000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FleXNet FX-4000 and is the answer not in the manual?

Mircom FleXNet FX-4000 Specifications

General IconGeneral
BrandMircom
ModelFleXNet FX-4000
CategoryMeasuring Instruments
LanguageEnglish