Check code
Abnormal points and detection methods Causes and checkpoints
AbnormalifovercurrentofDCbusorcompressorisdetectedbefore30
secondsafterthecompressorstartsoperating.
Closedstopvalve
Decreaseofpowersupplyvoltage
Looseness,disconnection,orwrongphaseof
compressorwiringconnection
Model selection error on indoor controller board or
outdoor multi controller circuit board
Defectivecompressor
Defectiveoutdoorpowercircuitboard
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
4100
(UF)
Compressorcurrentinterruption(Lockedcompressor)
Chart 1 of 2
Yes
Yes
Yes
No
No
No
Isthestopvalve(liquid/gas)fully
open?
Isthepowersupplyvoltagenormal?
Aretheysetproperly?
Openthestopvalve(liquid/gas)fully.
• Checkthelooseness,disconnection,or
breakageofcompressorwiring.
• Ensurepowersupplyfromthefacility.
(Checkforpowersupplyopenphase.)
Setthemodelselectionswitchcorrectly,
then restart.
Checkthestopvalve.
Checkthepowersupplyvoltage.
Checkifthemodelselectionswitchisset
correctly on the indoor controller board or
outdoor multi controller circuit board.
TurnthepowerOFFtocheckfor
looseness,disconnection,orwrongphase
ofcompressorwiringconnection.
Continuetothenextpage
64
65
OCH668B

Other manuals for Mitsubishi Electric City Multi PUMY-SP112VKM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric City Multi PUMY-SP112VKM and is the answer not in the manual?

Mitsubishi Electric City Multi PUMY-SP112VKM Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCity Multi PUMY-SP112VKM
CategoryAir Conditioner
LanguageEnglish

Related product manuals