Check code
6607
(A7)
No ACK error
Chart 3 of 4
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
Yes
Yes
No
No
No
Yes
Yes
No
The transmission line is connected
properly.
Itisnotexceedingthetolerance.
Checkthetransmissionlinewhetherit
exceedsthetoleranceornot.
Checkwhetherthecorrectkindof
transmission line is used or not.
Correctitwithinthetolerance,thenperform
theprocedure1.
Connectthetransmissionlineproperly,
thenperformtheprocedure1.
Istheabnormalityreproduced?
Isitsetproperly?
There is no abnormality on the AC unit.
Itmightbecausedbyanexternalnoise,socheckthe
transmission line to remove the factor(s).
Settheaddressproperly,thenperformthe
procedure1.
Checktheaddressswitchonthesourceof
abnormality.
Check the transmission line for a
disconnection and looseness
(on the terminal board and connector).
TurnthepowerOFFofindoor/outdoorunit,Fresh
Master, Lossnay and remote controller simultaneously
for2minutesormore,thenturnthepowerbackON.
Procedure 1:
Continuetothenextpage
88
89
OCH668B

Other manuals for Mitsubishi Electric City Multi PUMY-SP112VKM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric City Multi PUMY-SP112VKM and is the answer not in the manual?

Mitsubishi Electric City Multi PUMY-SP112VKM Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCity Multi PUMY-SP112VKM
CategoryAir Conditioner
LanguageEnglish

Related product manuals