[ I Read Before Servicing ]
- 12 -
HWE1708A GB
[9] Refrigerant Charging
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled
the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid
phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and be-
come unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
[10] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the
liquid state.)
Refer to "VIII [5] Refrigerant Leak."(page 198)
Cylinder with a siphon
Cylinder color R410A is pink.
Cylinder color R32 is light blue.
Refrigerant charging in the liquid state
Cylin-
der
liquid
Valve Valve
liquid
Cylin-
der
Cylinder without a siphon
0000002394.book 12 ペー 023年9月7日 木曜日 午後4時2

Table of Contents

Other manuals for Mitsubishi Electric CMB-WM-V-AA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric CMB-WM-V-AA and is the answer not in the manual?

Mitsubishi Electric CMB-WM-V-AA Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCMB-WM-V-AA
CategoryAir Conditioner
LanguageEnglish

Related product manuals