EasyManua.ls Logo

Mitsubishi Electric FX3U SERIES - Page 329

Mitsubishi Electric FX3U SERIES
948 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
327
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
12 Data Operation – FNC 40 to FNC 49
12.4 FNC 43 – SUM / Sum of Active Bits
11
FNC30-FNC39
Rotation and
Shift
12
FNC40-FNC49
Data Operation
13
FNC50-FNC59
High-Speed
Processing
14
FMC60-FNC69
Handy
Instruction
15
FNC70-FNC79
External FX I/O
Device
16
FNC80-FNC89
External FX
Device
17
FNC100-FNC109
Data
Transfer 2
18
FNC110-FNC139
Floating Point
19
FNC140-FNC149
Data
Operation 2
20
FNC150-FNC159
Positioning
Control
Caution
While the command input is OFF, the instruction is not executed.
The output of the number of bits in the ON status is latched in the previous status.
Program example
When X000 is ON, the number of bits in the ON status in D0 is counted, and stored to D2.
X000
S
D
The number of "1" in D0 is stored to D2.
FNC 43
SUM
D 0 D 2
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1
D 0 = K0 D 2 = K0
M8020=ON
M8020=OFF
32 16 8 4 2 1
D 0 = K21847 D 2 = K9
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Zero flag
Zero flag

Table of Contents

Other manuals for Mitsubishi Electric FX3U SERIES