•FX3U/FX3UC PLCs
•FX
3G PLCs (Standard mode)
Applied instruction Execution time Remarks
MOV instruction (FNC 12)
Execution time at rising edge of input: Execution time in ON status 1.22 μs in MOVP instruction
Non-execution time: Execution time in OFF status
Other applied instructions
Execution time at rising edge of input: Execution time in ON status + 0.45
μs
Non-execution time: Execution time in OFF status + 0.45 μs
Applied instruction Execution time Remarks
MOV instruction (FNC 12)
Execution time at rising edge of input: Execution time in ON status = 4.98 μs
Non-execution time: Execution time in OFF status = 0.8 μs
BCD instruction (FNC 18)
Execution time at rising edge of input: Execution time in ON status = 5.03 μs
Non-execution time: Execution time in OFF status = 0.75 μs
BIN instruction (FNC 19)
Execution time at rising edge of input: Execution time in ON status = 5.03 μs
Non-execution time: Execution time in OFF status = 0.75 μs
ADD instruction (FNC 20)
Execution time at rising edge of input: Execution time in ON status = 6.37 μs
Non-execution time: Execution time in OFF status = 0.75 μs
SUB instruction (FNC 21)
Execution time at rising edge of input: Execution time in ON status = 6.47 μs
Non-execution time: Execution time in OFF status = 0.75 μs
MUL instruction (FNC 22)
Execution time at rising edge of input: Execution time in ON status = 7.07 μs
Non-execution time: Execution time in OFF status = 0.75 μs
DIV instruction (FNC 23)
Execution time at rising edge of input: Execution time in ON status = 7.03 μs
Non-execution time: Execution time in OFF status = 0.75 μs
INC instruction (FNC 24)
Execution time at rising edge of input: Execution time in ON status = 3.48 μs
Non-execution time: Execution time in OFF status = 0.75 μs
DEC instruction (FNC 25)
Execution time at rising edge of input: Execution time in ON status = 3.48 μs
Non-execution time: Execution time in OFF status = 0.75 μs
WAND instruction (FNC 26)
Execution time at rising edge of input: Execution time in ON status = 6.42 μs
Non-execution time: Execution time in OFF status = 0.75 μs
WOR instruction (FNC 27)
Execution time at rising edge of input: Execution time in ON status = 6.42 μs
Non-execution time: Execution time in OFF status = 0.75 μs
WXOR instruction (FNC 28)
Execution time at rising edge of input: Execution time in ON status = 6.42 μs
Non-execution time: Execution time in OFF status = 0.75 μs
Other applied instructions
Execution time at rising edge of input: Execution time in ON status + 0.45 μs
Non-execution time: Execution time in OFF status + 0.45 μs