34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305
34.6 FNC 305 – FLSTRD / FX3U-CF-ADP status read
When is "K768 (H300)"
The FLSTRD instruction reads the version information of the CF-ADP.
When is "K1024 (H400)"
The FLSTRD instruction reads the error information (error flag).
When is "K1280 (H500)"
The FLSTRD instruction reads the error code and error code details for errors having occurred in the CF-ADP. Up
to 5 of the latest error codes and error code details can be stored.
Cautions
It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an
"FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
Setting items Description
Stores the version of CF-ADP.
(Example) K100 = Ver.1.00
Setting items Description
Error detection signal
b0 : The CompactFlash
TM
card is not mounted.
b1 : The CompactFlash
TM
card is full.
b2 : An error has occurred in the CF-ADP.
b3 : CF-ADP H/W error
b4 : CompactFlash
TM
card error
b5 to b15 : Not used
Setting items Description
Error code 1
+1
Error code details 1
+2
Error code 2
+3
Error code details 2
+4
Error code 3
+5
Error code details 3
+6
Error code 4
+7
Error code details 4
+8
Error code 5
+9
Error code details 5
S
D
S
D
S
D
D
D
D
D
D
D
D
D