912
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-1 Basic Instruction Execution Time
•FX3G PLCs (Extention mode)
Instruction
Execution time in ON status (μs) Execution time in OFF status (μs)
Remarks
16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction
Contact instructions
LD 0.42
1.68 μs in 2-step instruction
*1
1.68 μs in 3-step instruction
*3
LDI 0.42
1.68 μs in 2-step instruction
*1
1.68 μs in 3-step instruction
*3
LDP 2.72 2.68
3-step instruction
2.8 μs in execution in ON status
*3
2.76 μs in execution in OFF status
*3
LDF 2.76 2.72
3-step instruction
2.84 μs in execution in ON status
*3
2.8 μs in execution in OFF status
*3
AND 0.41
1.48 μs in 2-step instruction
*1
1.52 μs in 3-step instruction
*3
ANI 0.41
1.48 μs in 2-step instruction
*1
1.52 μs in 3-step instruction
*3
ANP 2.72 2.68
3-step instruction
2.8 μs in execution in ON status
*3
2.76 μs in execution in OFF status
*3
ANF 2.76 2.72
3-step instruction
2.8 μs in execution in ON status
*3
2.76 μs in execution in OFF status
*3
OR 0.42
1.6 μs in 2-step instruction
*1
1.6 μs in 3-step instruction
*3
ORI 0.42
1.6 μs in 2-step instruction
*1
1.6 μs in 3-step instruction
*3
ORP 2.72 2.68
3-step instruction
2.8 μs in execution in ON status
*3
2.76 μs in execution in OFF status
*3
ORF 2.76 2.72
3-step instruction
2.8 μs in execution in ON status
*3
2.76 μs in execution in OFF status
*3
Connection instructions
ANB 0.41
ORB 0.41
MPS 0.42
MRD 0.41
MPP 0.38
INV 0.38
MEP 1.73
MEF 1.81
Output instructions
OUT Y,M 0.42
1.52 μs in 2-step instruction
*2
1.56 μs in 3-step instruction
*3
OUT S 1.65 1.65
OUT T K 3.19 2.95
T246 to T319
3.47 μs in execution in ON status
2.82 μs in execution in OFF status