920
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-4 Applied Instruction Execution Time
Character string control
206 MIDR 25 + 0.59n + 0.68m 0.455
n: Character position
m: Number of characters
207 MIDW 25.8 + 0.3m + 0.44n 0.455
n: Character position
m: Number of stored
characters
208 INSTR 20.6 + 2.98m 0.585
m: Number of searched
characters
*1
209 $MOV 16 + 1.52n 0.325
*1. Number of characters from the head of the searched character string to detected character
Data operation 3
210 FDEL 43 + 0.95m ⎯⎯⎯
m: Number of data shifted
forward
*2
211 FINS 63 + 0.98m ⎯⎯⎯
m: Number of data shifted
backward
*3
212 POP 7.8 0.455
213 SFR 9.3 0.325
214 SFL 9.3 0.325
215 ⎯⎯⎯⎯
216 ⎯⎯⎯⎯
217 ⎯⎯⎯⎯
218 ⎯⎯⎯⎯
219 ⎯⎯⎯⎯
*2. m = (Number of data tables) - (Table position of deleted data)
Number of data tables: Present value of , table position of deleted data: n
*3. m = (Number of data tables) - (Table position of data insertion)
Number of data tables: Present value of , table position data insertion: n
Data comparison
220 ⎯⎯⎯⎯
221 ⎯⎯⎯⎯
222 ⎯⎯⎯⎯
223 ⎯⎯⎯⎯
224 LD= 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
225 LD> 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
226 LD< 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
227 ⎯⎯⎯⎯
228 LD<> 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
229 LD<= 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
230 LD>= 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
231 ⎯⎯⎯⎯
232 AND= 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
233 ADN> 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
234 AND< 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
235 ⎯⎯⎯⎯
236 AND<> 1.22 1.48 1.22 1.48
For details, refer to
Appendix B-6-2.
FNC
No.
Instruction
Execution time in ON status (μs) Execution time in OFF status (μs)
Remarks
16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction
D
D

Table of Contents