8 - 7
(5) Device
Number of points, latch range, and local device range are set for each device.
(To the next page)
Figure 8.5 Device
Table8.5 Device setting list
Item
Parameter 
No.
Description Setting range Default Reference
Device points
*1
2000H
Set the number of device points 
that is appropriate to the system.
X (8K), Y (8K), and S (8K)
*3
 are fixed.
Setting is available within the range of 
29K words in total, including the above 
fixed points (1.5K words).
• One device: Up to 32K points
• Total bit device points: Up to 64K 
points
•X: 8K
•Y: 8K
•M: 8K
•L: 8K
*2
•B: 8K
•F: 2K
• SB: 2K
•V: 2K
•S: 8K
*3
•T: 2K
•ST: 0K
•C: 1K
• D: 12K
•W: 8K
•SW: 2K
Section 9.1
Latch (1) start/end (Latch 
clear valid)
*2
2001H
Set a latch range (start and end 
device numbers), which can be 
cleared by remote latch clear 
operation.
Setting is available for only one range 
for each of B, F, V, T, ST, C, D, and W 
devices.
Blank Section 3.4, 6.3
Latch (2) start/end (Latch 
clear invalid)
*2
2002H
Set a latch range (start and end 
device numbers), which cannot be 
cleared by remote latch clear 
operation.
Setting is available for only one range 
for each of L, B, F, V, T, ST, C, D, and W 
devices.
Blank Section 3.4, 6.3
Local device start/end
*6
2003H
Set a range (start and end device 
numbers), which is used for a 
local device.
Setting is available for only one range 
for each of M, V, T, ST, C, D, and Z 
devices.
*5
Blank Section 9.14.2