495
APPENDICES
A
Appendix 2 List of Special Relay Areas
(19)Redundant power supply module information
*1 The "power supply 1" indicates the redundant power supply module mounted on the POWER 1 slot of the redundant
base unit (Q38RB/Q68RB/Q65WRB).
*2 The "power supply 2" indicates the redundant power supply module mounted on the POWER 2 slot of the redundant
base unit (Q38RB/68RB/Q65WRB).
*3 Modules whose serial number (first five digits) is "07032" or later
In a multiple CPU system, the serial number (first five digits) of all the CPU modules must be "07032" or later.
*4 Modules whose serial number (first five digits) is "10042" or later
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
SM1780
Power supply off
detection flag
OFF: No redundant
power supply
module with input
power OFF
detected
ON: Redundant power
supply module
with input power
OFF detected
• Turns on when one or more redundant
power supply modules with input power
off are detected.
• Turns on if any of SD1780 bits is on.
• Turns off if all bits of SD1780 are off.
• This relay turns off when the main base
unit is not the redundant main base unit
(Q38RB).
• When the multiple CPU system is
configured, the flags are stored only to the
CPU No.1.
S (Every
END
processing)
New
Qn(H)
*3
QnPH
*3
QnPRH
QnU
*4
SM1781
Power supply
failure detection
flag
OFF: No faulty
redundant power
supply module
detected
ON: Faulty redundant
power supply
module detected
• Turns on when one or more faulty
redundant power supply modules are
detected.
• Turns on if any of SD1781 bits is on.
• Turns off if all bits of SD1781 are off.
• This relay turns off when the main base
unit is not the redundant main base unit
(Q38RB).
• When the multiple CPU system is
configured, the flags are stored only to the
CPU No.1.
S (Every
END
processing)
New
Qn(H)
*3
QnPH
*3
QnPRH
QnU
*4
SM1782
Momentary
power failure
detection flag for
power supply 1
*1
OFF: No momentary
power failure
detected
ON: Momentary power
failure detected
• Turns on when a momentary power failure
of the input power supply to the power
supply 1 or 2 is detected one or more
times. After turning on, this relay remains
on even if the power supply recovers from
the momentary power failure.
• Turns off the flags (SM1782 and SM1783)
of the power supply 1 and 2 when the
CPU module starts.
• When the input power to one of the
redundant power supply modules turns
off, the corresponding flag turns off.
• This relay turns off when the main base
unit is not the redundant main base unit
(Q38RB).
• When the multiple CPU system is
configured, the flags are stored only to the
CPU No.1.
S (Every
END
processing)
New
Qn(H)
*3
QnPH
*3
QnPRH
QnU
*4
SM1783
Momentary
power failure
detection flag for
power supply 2
*2