EasyManua.ls Logo

Mitsubishi Electric R32MTCPU - Device Output: DOUT

Mitsubishi Electric R32MTCPU
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 OPERATION CONTROL PROGRAMS
4.11 Bit Device Controls
181
4
Device output: DOUT
Setting data
Usable Data
: Usable
Description, data type of result
Processing details
The data specified with (S) is output to the bit data specified with (D).
Specify a multiple of 16 as the device No. of the bit data specified with (D).
If the type of (S) is a 16-bit integer type, 16 points of the (S) data, starting at the least significant bit, are output in order to
the bit devices headed by the one specified with (D).
If the type of (S) is a 32-bit integer type, 32 points of the (S) data, starting at the least significant bit, are output in order to
the bit devices headed by the one specified with (D).
Operation error
An operation error will occur if:
(D) or (S) is an indirectly specified device and its device No. is outside the range.
(D) is an indirectly specified device and its device No. is not a multiple of 16.
Program example
Program which outputs the data of D0 to Y0-YF
Format Number of basic steps Usable steps
F/FS G
DOUT (D),(S) 8 
Setting
data
Usable Data
Bit
device
Word device Constant Calculation
expression
Bit
conditional
expression
Comparison
conditional
expression
16-bit
integer
type
32-bit
integer
type (L)
64-bit
floating
point
type (F)
16-bit
integer
type
(K/H)
32-bit
integer
type
(K/H, L)
64-bit
floating
point
type (K)
(D) 
(S) 
Setting data Description Data type of result
(D) Output destination bit data Batch bit
(S) Output source data
DOUT Y0, D0
0D0
111001
b15 b0
YF Y0
000100 111
0
111001000100 111