1 FUNCTIONS
1.5 IP Packet Transfer Function
43
1
Rules for the IP address setting
IP addresses specified for the IP packet transfer function need to satisfy the following rules.
*1 Set the Nos. according to the range applicable to the Ethernet device used. The range may not apply depending on the Ethernet device.
Check the specifications of the Ethernet device used.
Device to be set Setting range of the IP address
First and second octets Third octet Fourth octet
Ethernet device
0.0 to 223.255
*1
(Same Nos. for the request source
device, request destination device,
and modules between them)
, ,
1 to 239
*1
(Same No. for the Ethernet device
and the Ethernet-equipped module)
1 to 120
*1
Ethernet-equipped module connected
to the Ethernet device
Simple Motion module ,
Automatically set (network No. of the
own station)
1 to 239
Automatically set (station No. of the
own station)
1 to 120
125 (125 is always set in the
master station.)
Remote head module
Automatically set (Same value as the
master station)
0.0 to 223.255
Simple Motion module on the
communication path (not connected to
an Ethernet device)
IP address setting not required