APP - 17
APPENDICES
*: Usable with AnN and AnA which are compatible with SFC.
For the AnN and AnA which are compatible with SFC, refer to the MELSAP-II Programming Manual.
Table App2.1 Special Relay List (Continue)
Number Name Description Details Applicable CPU
*2
M9103
Consecutive
step transfer
enable/disable
OFF:Consecutive step
transfer disable
ON: Consecutive step
transfer enable
Selects consecutive or step-by-step transfer of
steps of which transfer conditions are established
when all of the transfer conditions of consecutive
steps are established.
ON: Consecutive transfer is executed.
OFF: One step per one scan is transferred.
Usable with AnN*,
AnA*, AnU,
A2AS, QCPU-A
(A Mode), A2C,
A0J2H, AnS,
AnSH, A1FX and
A52G.
M9104
Consecutive
transfer
prevention flag
OFF:Transfer complete
ON: Transfer
incomplete
Turned on when consecutive transfer is not
executed with consecutive transfer enabled.
Turned off when transfer of one step is completed.
Consecutive transfer of a step can be prevented by
writing an AND condition to corresponding M9104.
Usable with AnN*,
AnA*, AnU,
A2AS, QCPU-A
(A Mode), A2C,
A0J2H, AnS,
AnSH, A1FX and
A52G.
*2
M9108
Step transfer
monitoring timer
start
(corresponds to
D9108)
OFF:Monitoring timer
reset
ON: Monitoring timer
reset start
Turned on when the step transfer monitoring timer
is started. Turned off when the monitoring timer is
reset.
Usable with AnN*,
AnA*, AnU,
A2AS, QCPU-A
(A Mode), A2C,
A0J2H, AnS,
AnSH, A1FX and
A52G.
*2
M9109
Step transfer
monitoring timer
start
(corresponds to
D9109)
*2
M9110
Step transfer
monitoring timer
start
(corresponds to
D9110)
*2
M9111
Step transfer
monitoring timer
start
(corresponds to
D9111)
*2
M9112
Step transfer
monitoring timer
start
(corresponds to
D9112)
*2
M9113
Step transfer
monitoring timer
start
(corresponds to
D9113)
*2
M9114
Step transfer
monitoring timer
start
(corresponds to
D9114)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi A2SHCPU (S1) and is the answer not in the manual?

Mitsubishi A2SHCPU (S1) Specifications

General IconGeneral
BrandMitsubishi
ModelA2SHCPU (S1)
CategoryController
LanguageEnglish

Related product manuals