–35–
(2) Nomenclature display of unit
• At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the
unit is displayed with two English characters.
Display Type (Attribute) of unit/controller
Indoor unit connectable to remote controller
Outdoor unit
BC controller (Master)
BC controller (Slave)
Local remote controller
System controller (MJ)
Lossnay Controller
[Description of registration/deletion/retrieval]
• Operations to be performed by the remote controller are given below. Please see the related paragraphs for details.
1 Group registration of indoor unit
• The group of the indoor units and operating remote controller is formed/registered.
• It is used for the group operation of indoor units.
2 Retrieval/identification of group registration information of indoor units
• The address of the registered indoor units in a group is retrieved (identified).
3 Retrieval/identification of registration information
• The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).
4 Deletion of group registration information of indoor units
• The registration of the indoor units under group registration is released (deleted).
5 Deletion of the address not existing
• This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by
a setting error during test run, or previous memory remaining after an alteration/modification of the group composi-
tion.
Caution:
When MELANS (G50-A for example) is connected to the system, do not conduct a group/pair registration using the
remote controller. The group/pair registration should be conducted with MELANS. (For details, refer to the instruc-
tion prepared for MELANS)