PARAMETERS
107
<Setting>
Pr. 75
Setting
Reset Selection
PU Disconnection
Detection
PU Stop
Selection
0
Reset input normally enabled.
1
Reset input enabled only when the
protective function is activated.
If the PU is disconnected,
operation will be continued.
2
Reset input normally enabled.
3
Reset input enabled only when the
protective function is activated.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
Pressing the
STOP
RESET
key
decelerates the
inverter to a stop
only in the PU
operation mode.
14
Reset input normally enabled.
15
Reset input enabled only when the
protective function is activated.
If the PU is disconnected,
operation will be continued.
16
Reset input normally enabled.
17
Reset input enabled only when the
protective function is activated.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
Pressing the
STOP
RESET
key
decelerates the
inverter to a stop
in any of the PU,
external and
communication
operation modes.
How to make a restart after a stop by the
STOP
RESET
key on the PU
(1) Control panel (FR-PA02-
02
)
1) After completion of deceleration to a stop, switch off the STF or STR signal.
2) Press the
MODE
key two times* to display .
Note: When Pr. 79 = 3, press the
MODE
key three times to display . Then,
press the
key and proceed to step 3).
(For the monitor screen) .........Refer to page 52 for the monitor display provided
by pressing the
MODE
key.
3) Press the
SET
key.
4) Switch on the STF or STR signal.
(2) Parameter unit (FR-PU04)
1) After completion of deceleration to a stop, switch off the STF or STR signal.
2) Press the
EXT
key.
3) Switch on the STF or STR signal.
Time
Stop and restart example for external operation
STF ON
(STR) OFF
Speed
Control panel
key
SET
key
STOP
RESET
The other way of making a restart other than the above method is to perform a
power-reset or to make a reset with the inverter reset terminal.