3.3.3 PU operation mode (Operation using the control panel)
(
1
)
 Using the control panel (FR-PA02
-0
2
) for operation at 60Hz with
digital frequency setting
Operation command: 
RUN
 key or 
FWD
 / 
REV
 key of the control panel (FR-PA02
-02
)
Frequency setting: 
 /   key
Related parameters: Pr. 79 "operation mode selection".
By repeating step 2 below during motor run, speed can be varied.
Step Description Image
1
Power on 
→
 Operation mode check
Switch power on, refer to page 54, and set "1" in Pr. 79
"operation mode selection".
The [PU] indication is lit.
ON
Hz
A
PU
RUN
MON
EXT
2
Running frequency setting
Set the running frequency to 60Hz.
1) Refer to page 52 and select the frequency setting mode
with the 
MODE
 key.
2) Refer to page 53, make setting with the 
 /   key,
and write the setting with the 
SET
 key.
(or)
MODE SE T REV
STOP
RESET
FWD
Hz
A
PU
RUN
MON
EXT
3
Start
Press the 
RUN
 key (or 
FWD
 / 
REV
 key). The monitoring
mode is automatically selected and the output frequency is
displayed.
The [RUN] indication is lit to indicate forward rotation, or
flickers to indicate reverse rotation.
RUN
FWD REV
MODE SET REV
STOP
RESET
FWD
Hz
A
PU
RUN
MON
EXT
4
Stop
Press the 
STOP
RESET
 key.
The motor is decelerated to a stop.
The [RUN] indication goes off.
Hz
PU
MON
(
2
)
 PU jog operation
Hold down the 
RUN
 (or 
FWD
 or 
REV
) key to perform operation, and release it to stop.
1) Set Pr. 15 "jog frequency" and Pr. 16 "jog acceleration/deceleration time".
2) Select the PU jog operation mode. (Refer to page 55.)
3) Hold down the 
RUN
 or 
FWD
, 
REV
 key to perform operation.
(If the motor remains stopped, check Pr. 13 "starting frequency". The motor will not
start if its setting is lower than the starting frequency.