<Operating conditions>
!
The motor capacity is equal to or one rank lower than the inverter capacity.
!
The number of motor poles is any of 2, 4, and 6. (4 poles only for the constant-
torque motor)
!
Single-motor operation (one motor for one inverter) is performed.
!
The wiring length between the inverter and motor is within 30m (98.42 feet). (If the
length is over 30m (98.42 feet), perform offline auto tuning with the cables wired.)
<Setting>
(
1
)
General-purpose magnetic flux vector control
!
By setting the capacity of the motor used in Pr. 80, you can choose general-purpose
magnetic flux vector control.
Parameter
Number
Setting Description
9999 V/F control
80
0.1 to 7.5/
0.2 to 7.5
(Note)
Set the motor capacity applied.
General-
purpose
magnetic flux
vector control
Note: The setting range changes with the inverter: 0.2kW to 7.5kW, 9999 for the
400V class.
!
When using Mitsubishi's constant-torque motor (SF-JRCA), set "1" in Pr. 71. (When
using the SF-JRC, perform the offline auto tuning.)