PARAMETERS
66
Func-
tion
Param-
eter
Number
Name
Setting
Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Custo-
mer
Setting
117 Station number 0 to 31 1 0 121
118 Communication speed 48, 96, 192 1 192 121
119 Stop bit length
0, 1 (data
length 8)
10, 11 (data
length 7)
1 1 121
120
Parity check
presence/absence
0, 1, 2 1 2 121
121
Number of communication
retries
0 to 10,
9999
1 1 121
122
Communication check
time interval
0, 0.1 to
999.8 s, 9999
0.1 s 9999 121
123 Waiting time setting
0 to 150,
9999
1 9999 121
Communication functions
124
CR
⋅
LF presence/absence
selection
0, 1, 2 1 1 121
128 PID action selection 0, 20, 21 1 0 134
129 PID proportional band
0.1 to
1000%,
9999
0.1% 100% 134
130 PID integral time
0.1 to 3600 s,
9999
0.1 s 1 s 134
131 Upper limit
0 to 100%,
9999
0.1% 9999 134
132 Lower limit
0 to 100%,
9999
0.1% 9999 134
133
PID action set point for PU
operation
0 to 100% 0.01% 0% 134
PID control
134 PID differential time
0.01 to
10.00 s,
9999
0.01 s 9999 134
145 Parameter for option (FR-PU04).
Additional
function
146 Parameter set by manufacturer. Do not set.
150
Output current detection
level
0 to 200% 0.1% 150% 142
151
Output current detection
period
0 to 10 s 0.1 s 0 142
152
Zero current detection
level
0 to 200.0% 0.1% 5.0% 143
Current detection
153
Zero current detection
period
0.05 to 1 s 0.01 s 0.5 s 143
156
Stall prevention operation
selection
0 to 31,100 1 0 144
Sub
function
158
AM terminal function
selection (Note 10)
0, 1, 2 1 0 92
160
User group read selection
0, 1, 10, 11 1 0 146
168
Additional
function
169
Parameters set by manufacturer. Do not set.
Initial
monitor
171
Actual operation hour
meter clear
0
0 148
Parameter List