PARAMETERS
68
Func-
tion
Param-
eter
Number
Name
Setting
Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Custo-
mer
Setting
900
FM terminal calibration
(Note 9)
  
156
901
AM terminal calibration
(Note 10)
  
158
902
Frequency setting voltage
bias
0 to
10V
0 to
60Hz
0.01Hz 0V 0Hz 160
903
Frequency setting voltage
gain
0 to
10V
1 to
400Hz
0.01Hz 5V 60Hz 160
904
Frequency setting current
bias
0 to
20mA
0 to
60Hz
0.01Hz
4
mA
0Hz 160
905
Frequency setting current
gain
0 to
20mA
1 to
400Hz
0.01Hz
20
mA
60Hz 160
990
Calibration functions
991
Parameter for option (FR-PU04).
Note:1. Indicates the parameter of which setting is ignored when the general-
purpose magnetic flux vector control mode is selected.
2. Since calibration is made before shipment from the factory, the settings differ
slightly between inverters. The inverter is preset to provide a frequency
slightly higher than 60Hz.
3. When the control panel is used and the setting is 100Hz or more, the setting
increments are 0.1Hz.
The setting increments are 0.01Hz when the communication made.
4. The setting depends on the inverter capacity: (0.1K to 3.7K)/(5.5K to 7.5K).
5. Set to 85% of the rated inverter current for the 0.1K to 0.75K.
6. If "2" is set in Pr. 77 (parameter write inhibit selection), the setting cannot be
changed during operation.
7. The half-tone screened parameters allow their settings to be changed during
operation if "0" (factory setting) has been set in Pr. 77 (parameter write
inhibit selection). (However, the Pr. 72 and Pr. 240 values may be changed
during PU operation only.)
8. The setting range changes with the inverter: 0.2kW to 7.5kW, 9999 for the
400V class.
9. Pr. 249 and Pr. 900 are not available for the 400V class.
10. Setting may be made on the 400V class inverter only.
11. The setting depends on the inverter capacity: 4% for the FR-E540-5.5K and
7.5K-NA.
12. For the FR-E540-5.5K and 7.5K-NA, the factory setting is 10s.
4