FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions
11 Batch Data Positioning Mode (TBL Instruction)
11.1 Instruction Format
B - 139
A
Common Items
B
Built-in 
Positioning 
Functions
Apx.
Example 
Connection
11. Batch Data Positioning Mode (TBL Instruction)
If GX Developer Ver.8.23Z or later is used, the positioning instructions 
shown below can be preliminarily set in the positioning tables.  After that, 
if a table is specified, the positioning operation of the specified table will 
be performed. 
*1. Only available for 
FX3U and FX3UC PLCs.
11.1 Instruction Format
1. Instruction Format
2. Data setting
3. Devices
1 : Specify Y000, Y001, or Y002
*1
 transistor output from the main unit, or specify Y000, Y001, Y002
*3
,
 
or 
Y003
*3
 from a high-speed output special adapter
*2
.
*1. Y002 is not available in 14-point and 24-point type 
FX3G PLC.
*2. High-speed input/output special adapters can be connected only to the 
FX3U PLC.
*3. To use Y002 and Y003 with a high-speed output special adapter, connect a second high-speed output
special adapter.
Point:
To use an FX
3U Series main unit of relay output type, be sure to connect a high-speed output special adapter.  
Differential line drive type outputs will be used for the outputs of the high-speed output special adapter.
Instruction Description
DVIT
*1
(FNC151)
One-speed interrupt constant quantity feed (Interrupt positioning)
PLSV(FNC157) Variable speed operation (Variable Speed Pulse Output)
DRVI(FNC158)
1-speed 
positioning
Drive to Increment
DRVA(FNC159) Drive to Absolute
Operand type Description Data type
Specifies the pulse output number. Bit
n Specifies the table number (1 to 100) to be executed. BIN 32-bit
Operand
type
Bit device Word device Others
System user Digit designation System user
Special 
unit
Index
Con-
stant
Real 
num-
ber
Char-
acter 
string
Pointer
XYMTCSD.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E ""P
1
n
33
32-bit
instruction
17 steps
DTBL
Continuous
execution
type
Instruction
symbol
Execution condition
-
16-bit
instruction
-
-
Instruction
symbol
Execution condition
FNC 152
TBL
TABLE
D
Command
input
FNC152
DTBL
D n
D
D