D-11
FX Series PLC User's Manual - Data Communication Edition
Computer Link
2 Specifications
2.2 Link Specifications
A
Common Items
B
N:N Network
C
Parallel Link
D
Computer Link
E
Inverter
Communication
F
Non-Protocol
Communication
(RS/RS2 Instruction)
G
Non-Protocol
Communication 
(FX
2N
-232IF)
H
Programming
Communication
I
Remote 
Maintenance
Apx.
Discontinued
models
2.2.2 Applicable device ranges
The tables below show devices and device number ranges applicable for the device memory access.
• Construct each of the BR, BW, BT, WR, WW, and WT commands in five characters.
• Construct each of the QR, QW, and QT commands in seven characters.
1. Bit devices
FX PLCs do not support timer coils (TC) and counter coils (CC).
Device
Device number range (character)
Device 
number 
expression
Decimal/
Octal
Available commands
FX1S FX0N
FX2(FX), 
FX
2C
FX1N, 
FX
1NC
FX2N, 
FX
2NC
FX3U, 
FX
3UC
BR, 
BW, BT
WR, 
WW, WT
QR, 
QW, QT
Input 
relay 
(X)
X0000 to 
X0017
X0000 to 
X0177
X0000 to 
X0267
X0000 to 
X0177
X0000 to 
X0337
X0000 to 
X0377
Octal
—
—
X000000 
to 
X000377
——
Output 
relay 
(Y)
Y0000 to 
Y0015
Y0000 to 
Y0177
Y0000 to 
Y0267
Y0000 to 
Y0177
Y0000 to 
Y0337
Y0000 to 
Y0377
—
—
Y000000 
to 
Y000377
——
Auxiliary 
relay 
(M)
M0000 to M0511 M0000 to M1535
M0000 to 
M3071
M0000 to 
M7679
Decimal
—
—
M000000 
to 
M007679
——
State 
relay 
(S)
S0000 to S0127 S0000 to S0999
S0000 to 
S4095
—
S000000 
to 
S004095
——
Special 
auxiliary 
relay 
(M)
M8000 to M8254 M8000 to M8255
M8000 to 
M8511
—
—
M008000 
to 
M008511
——
Timer 
contact 
(T)
TS000 to TS063 TS000 to TS255
TS000 to 
TS511
——
—
TS00000 
to 
TS00511
———
Counter 
contact 
(C)
CS000 to 
CS031
CS235 to 
CS255
CS000 to 
CS031
CS235 to 
CS254
CS000 to CS255
CS000 to 
CS255
 ——
—
CS00000 
to 
CS00255
———
1 character
2 characters for timer or counter
4 characters
3 characters for timer or counter
Device                  +                  Device number             = 5 characters
1 character
2 characters for timer or counter
6 characters
5 characters for timer or counter
Device                  +                  Device number             = 7 characters