328
-
'20 • KX-T-373
0.8
Detectable area
φA
Ceiling height “h”
High of the ceiling h[m]
2.7 3.5 4.0
Detectable area φA[m]
4.5 6.4 7.6
Detectable area φB[m]
6.4 8.3 9.5
Detectable area
φB
Notes
(1) The recommended height, is lower than 4m for motion sensor.
When the installation height is higher, motion detection accuracy
might be reduced.
(2) Connenction wiringprepare on sitefor signal wiring is
0.2mm
2
× 3 cores wire or moreRed,White,Black and maximum
total extension 8m.
(3) Motion sensor kit can be installed on the wall, but recommend
installing is the ceiling plane.
(4) In the case of wall installation, the detectable area is 5m in front
and about 100° left and right.
(5) Refer to the installation sheet for details.
Floor face
Ceiling plane
Unit:mm
80
57 12
74
37 37
20
177.5
17
120
φ15 (Ciling hole)
Wiring pass hole
23 2
20 5
Case of wiring out to the side face,
cut thin wall part
Case of wiring out
to the back
Switch box
Lockscrew of cover
(Ensure installation
space)
(Case hold)
12.2 Motion sensor kit (LB-KIT2)
(1) Specification
PJZ000Z341
External dimensions
Detectable area
(3) FDK series(LB-KIT2)
(a) Specification
PJZ000Z341