- 60 -
Communication de-
mand capacity
0 - 255
Abnormal thermistor
display
1 - 3,
FAN output at abnor-
mal stop
0 - 100
Outdoor Condenser/
evaporater temp tem-
perature at abnormal
stop
39 - 88
Discharge super heat
SHd at abnormal stop
0 - 216
Cooling: Outdoor TH2-
Outdoor TH3
Heating:Outdoor TH2-
Indoor TH3
(average)
Sub cool Sc at abnor-
mal stop
0 - 130
Cooling: Outdoor TH3-
Outdoor TH1
Heating:Indoor TH3
(average) -In-
door TH2 (av-
erage)
0 - 255
When communication demand not set: 100 %
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
1
←→ 100
1 - 3,
1: Outdoor liquid temp thermistor (TH1)
2: Outdoor discharge temp thermistor (TH2)
3: Outdoor condenser/evaporater temp thermistor (TH3)
: No abnormal thermistor
0 - 100
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
←→ 00
39 - 88
(When 0 °C or lower, “–”and temperature are displayed
alternately.)
<Example> When 10,
every other second
←→ 10
0 - 216
(When 100 °C or higher, 100s digit and 10s and units
digits are displayed alternately.)
<Example> When 150,
every other second
←→ 50
0 - 130
(When 100 °C or higher, 100s digit and 10s and units
digits are displayed alternately.)
<Example> When 100,
every other second
1
←→ 00
%
%
°C
°C
°C
SW2 setting Display contents Description of display Unit
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456