Indoor unit control
status
Indoor 1, 2
Indoor unit control
status
Indoor 3, 4
Condenser/evaporater
temperature (TH3)
Outdoor unit control
status
Discharge super heat
SHd
0 - 216
Cooling: Outdoor TH2 -
Outdoor TH3
Heating:Outdoor TH2
- Indoor TH3
(Average)
Sub cool Sc
0 - 130
Cooling: Outdoor TH3
- Outdoor
TH1
Heating:Indoor TH3
(Average) -
Indoor TH2
(Average)
Target sub cool step N
1 - 5
–39 - 88
(When 0 °C or lower, “–”and temperature are displayed
alternately.)
<Example> When –10,
every other second
–
←→ –10
0 - 216
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 150,
every other second
1
←→ 50
0 - 130
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
1
←→ 00
1 - 5
–
–
°C
–
°C
°C
–
SW2 setting Display contents Description of display Unit
Indoor unit No.1
Indoor unit No.3
Indoor unit No.2
Indoor unit No.4
Control mode
Indoor unit
Ordinary
Hot adjustment
Defrosting
—
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
Display
0
1
2
3
4
5
6
7
Outdoor unit
←
←
←
←
←
←
←
←
Control mode display system
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
Indoor unit No.1
Indoor unit No.3 Outdoor unit
Indoor unit No.2
Indoor unit No.4
Control mode
Indoor unit
Ordinary
Hot adjustment
Defrosting
—
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
Display
0
1
2
3
4
5
6
7
Outdoor unit
←
←
←
←
←
←
←
←
Control mode display system
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456