26
1
3
2
2
3
1
Red
White
Black
Relay connector
Protector
OFF:125i5:
ON :79i15:
4
5
2
361
Orange
Red
Pink
Yellow Brown Blue
M
Parts name Check points
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Fan motor
160"
Measure the resistance between the terminals using a tester.
Contactor
(for heater)
(Only PKH)
Abnormal
Open or short
61
88H
Normal
Abnormal
Open or short
Red–Black
White–Black
Motor terminal
or
Relay connector
120.5"
111.3"
Normal
Open or short
Abnormal
Brown–Yellow
Brown–Blue
Red–Orange
Red–Pink
Connector
Normal
186~214"
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Vane motor
Measure the resistance of each heater element by using a tester.
Heater
(Only PKH)
Normal
Abnormal
72"
800W 240V
Open or short
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
(Refer to <Thermistor Characteristic graph>
for a detail.)
Room temperature
thermistor (TH1)
Pipe temperature
thermistor (TH2)
Condenser/evaporator
temperature thermistor
(TH5)
Normal
4.3k"~9.6k"
Abnormal
Open or short
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (k")
<Thermistor Characteristic graph>
Room temperature thermistor(TH1)
Pipe temperature thermistor(TH2)
Condenser/evaporator temperature
thermistor(TH5)
Thermistor R0=15kΩ ±3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
0: 15kΩ
10: 9.6kΩ
20: 6.3kΩ
25: 5.4kΩ
30: 4.3kΩ
40: 3.0kΩ
Thermistor for
lower temperature
1
273+t
1
273
9-6. HOW TO CHECK THE PARTS
PKH-P35GALH, PKH-P50GALH
PKA-RP35GAL, PKA-RP50GAL
OC330--1.qxp 05.5.9 1:30 PM Page 26