Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air
temperature
Discharge air temperature
Intake air
temperature
SHF
BF
Mode
Total
W
kW
V
A
V
A
MPa
(kgf/F)
MPa
(kgf/F)
°C
°C
°C
m
°C
°C
°C
°C
°C
PLH-3AAK(H) PLH-4AAK(H) PLH-5AAK(H) PLH-6AAK(H)Service Ref.
Cooling
7,700
3.32
Heating
8,400
3.11
13.82/5.16
2.01
(20.5)
0.51
(5.2)
84
41
3.9
5
27
19
13.2
35
24
0.74
0.12
12.89/4.81
1.89
(19.3)
0.42
(4.3)
77
-2.0
5
20
15
42.8
7
6
0.81 0.81
PLH-3AAK(H)
1, 50
240
PLH-4AAK(H)
1, 50
240
PLH-5AAK(H)
1,50
240
PLH-6AAK(H)
1,50
240
PUH-3VKA.TH
PUH-3YKA.TH
1/3,50
240/415
Cooling
9,700
3.46
Heating
10,400
3.45
5.24
1.81
(18.5)
0.49
(5.0)
80
41
10.5
5
27
19
13.7
35
24
0.79
0.08
5.22
1.73
(17.6)
0.36
(3.7)
75
1.0
5
20
15
39.9
7
6
1.25 1.25
PUH-4YKSA.TH
3,50
415
Cooling
12,400
4.51
Heating
14,000
4.46
6.89
1.85
(18.9)
0.44
(4.5)
76
46
4.0
5
27
19
12.5
35
24
0.73
0.10
6.81
1.94
(19.8)
0.36
(3.7)
81
1.1
5
20
15
45.5
7
6
1.43 1.43
PUH-5YKSA.TH
3,50
415
Cooling
14,000
5.07
Heating
16,100
4.92
7.74
1.90
(19.4)
0.42
(4.3)
74
39
4.6
5
27
19
11.2
35
24
0.71
0.06
7.50
2.01
(20.5)
0.37
(3.8)
76
0.3
5
20
15
49.8
7
6
1.64 1.64
PUH-6YKSA.TH
3,50
415
Electrical circuitRefrigerant circuit
Indoor
side
Outdoor
side
D.B.
W.B.
D.B.
D.B.
W.B.
Air flow
Air speed
Coverage range
K/
mim(CFM)
m/W
m
PLH-4AAK(H)
28(990)
4.9
7.4
PLH-3AAK(H)
20(705)
4.0
5.7
PLH-6AAK(H)
30(1,060)
6.6
8.9
PLH-5AAK(H)
30(1,060)
5.2
7.9
Standard
5. STANDARD OPERATION DATA
6. OUTLET AIR SPEED AND COVERAGE RANGE
wThe air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
The unit of pressure has been changed to Mpa based on the international SI system.
The conversion factor is : 1(Mpa)=10.2(kgf/
FF
)
OC360--1.qxp 06.2.24 1:56 PM Page 25