34
Standard
High
ceiling
Air flow
Air speed
Coverage range
Air flow
Air speed
Coverage range
m
3
/min
m/sec.
m
m
3
/min
m/sec.
m
16.0
5.6
6.0
17.0
5.9
6.4
PLH-P1.6KAH.UK
PLH-P1.6KAH
1.UK
PLH-P2KAH.UK
PLH-P2KAH1.UK
PLH-P2.5KAH.UK
PLH-P2.5KAH1.UK
16.0
5.6
6.0
17.0
5.9
6.4
17.0
5.9
6.4
18.0
6.3
6.8
5. OUTLET AIR SPEED AND COVERAGE RANGE
w The air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
TotalElectrical circuitRefrigerant circuitIndoor side
Outdoor
side
Service Ref.
SHF
BF
V
A
MPa
MPa
°C
°C
°C
m
°C
°C
°C
°C
°C
Mode
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
1/3 , 50
240/415
1/3 , 50
240/415
1/3 , 50
240/415
7.36/2.49
2.08
0.50
87.1
48.3
12
5
27
19
16.3
35
24
0.80
0.26
7.59/2.56
2.45
0.44
84.5
47
2
5
20
15
36.5
7
6
—
—
10.26/3.70
2.31
0.48
87.8
53.4
4.5
5
27
19
15.0
35
24
0.74
0.22
10.57/3.82
2.50
0.46
93.2
53
0.8
5
20
15
40.0
7
6
—
—
11.90/4.48
1.95
0.50
77.5
48.5
6.3
5
27
19
13.5
35
24
0.75
0.12
(19.9)
(5.1)
(22.5)
(4.3)
(23.6)
(4.9)
(25.5)
(4.7)
(21.2)
(5.1)
(kgf/F)
(kgf/F)
(25.0)
(4.5)
11.51/4.34
2.21
0.42
83.4
50
0.8
5
20
15
43.7
7
6
—
—
Indoor unit Service Ref.
PLH-P1.6KAH.UK
PLH-P1.6KAH
1.UK
PLH-P1.6KAH.UK
PLH-P1.6KAH
1.UK
PLH-P2KAH.UK
PLH-P2KAH
1.UK
PLH-P2KAH.UK
PLH-P2KAH
1.UK
PLH-P2.5KAH.UK
PLH-P2.5KAH
1.UK
PLH-P2.5KAH.UK
PLH-P2.5KAH
1.UK
Capacity
Input
W
kW
Cooling
4,400
1.82
Heating
5,000
1.89
Cooling
5,300
2.44
Heating
5,950
2.40
Cooling
6,300
2.63
Heating
7,400
2.57
D.B.
W.B.
D.B.
D.B.
W.B.
V
A
Phase,Hz
Volts
Amperes
1,50
240
1,50
240
1,50
240
0.64 0.45 0.65 0.45 0.61 0.45
Outdoor unit Service Ref.
PUH-P1.6VGAA.UK
PUH-P1.6YGAA.UK
PUH-P2VGAA.UK
PUH-P2YGAA.UK
PUH-P2.5VGAA.UK
PUH-P2.5YGAA.UK
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/
ff
)
OC235B---2.qxp 04.9.29 3:23 PM Page 34