SW2 setting
Display detail
Explanation for display Unit
The black square (■) indicates a switch position.
74
1
ON
2 3 4 5 6
Liquid temperature (TH3)
−40 to 90
−40 to 90
(When the coil thermistor detects 0: or below, “-”
and temperature are displayed by turns.)
(Example) When −10:;
0.5 s 0.5 s 2 s
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Comp. surface temperature (TH32)
3 to 217 <SP125/140>
−52 to 221 <SP100>
Output step of outdoor FAN
0 to 10
The number of ON / OFF times of com-
pressor
0 to 9999
Compressor integrating operation times
0 to 9999
3 to 217 <SP125/140>
−52 to 221 <SP100>
(When the discharge thermistor detects 100 : or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105 :;
0.5 s 0.5 s 2 s
:
Step
100 times
10 hours
0 to 10
0 to 9999
(When the number of times is 100 or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 42500 times (425 ×100 times);
0.5 s 0.5 s 2 s
0 to 9999
(When it is 100 hours or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 2450 hours (245 × 10 hours);
0.5 s 0.5 s 2 s
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Compressor operating current
0 to 50
LEV-A opening pulse
0 to 480
0 to 50
Note: Omit the figures after the decimal fractions.
0 to 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 s 0.5 s 2 s
A
Pulse
Error postponement code history (1)
of outdoor unit
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
Code
display
10
1
ON
2 3 4 5 6
Compressor operating frequency
0 to 255
0 to 255
(When it is 100 Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125 Hz;
0.5 s 0.5 s 2 s
Hz
1
05
4
25
2
45
1
25
1
50
1
ON
2 3 4 5 6
OCH566A