76
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Capacity setting display
Displayed as an outdoor capacity code.
Code
display
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoor unit setting information
Indoor liquid pipe temperature (TH2(1))
Indoor 1
−39 to 88
Code
display
:
−39 to 88
(When the temperature is 0: or less, “-” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
Indoor intake temperature (TH1)
8 to 39
Capacity
SP100
SP125
SP140
Code
20
25
28
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P /
Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 :
Single phase
2 :
3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example) When heat pump, 3 phase and defrosting
(normal) are set up, “20” is displayed.
1
ON
2 3 4 5 6
Indoor cond./eva. temperature (TH5(1))
Indoor 1
−39 to 88
−39 to 88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
:
:
8 to 39
1
ON
2 3 4 5 6
The number of connected indoor units
Unit
0 to 1
(The number of connected indoor units are dis-
played.)
The black square (■) indicates a switch position.
1
ON
2 3 4 5 6
:
1
ON
2 3 4 5 6
Indoor setting temperature
17 to 30
Outdoor 2-phase pipe temperature (TH6)
−39 to 88
17 to 30
−39 to 88
(When the temperature is 0: or less, “-” and
temperature are displayed by turns.)
:
OCH566A