7 - 9 7 - 9
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.2 When industrial shipment setting is used and initial setting was made with sequence
program
(1) Conversion disable
(a) Disable the conversion by the following procedures.
1) Set the A/D conversion enable/disable setting (buffer memory address
0: Un\G0) for all channel conversion disable (F
H
).
2) Turn on Operating condition setting request (Y9) to stop the
conversion.
3) Operating condition setting completed flag (X9) is turned off.
4) Check that the conversion stops with the actual analog output value.
5) Turn off Operating condition setting request (Y9).