3 - 8 3 - 8
MELSEC-Q
3 SPECIFICATIONS
POINT
(1) Set within the analog input range and digital output range for each input
range.
If these ranges are exceeded, the resolution and accuracy may not fall within
the performance specifications. (Avoid the use of dotted areas of Fig. 3.2.)
(2) Do not input an analog input current of -30mA or less, or +30mA or more.
Doing so can cause the breakdown of the elements.
(3) Set the offset/gain values for the user setting range within a range in which
the following conditions are satisfied.
(a) Gain value
20mA, offset value 0mA
(b) { (gain value) - (offset value) } > 9.70mA
(4) When an analog value that exceeds the range of the digital output value is
entered, the digital output value will be fixed at the maximum or minimum
value.
Analog input
range setting
Digital output value (32 bits) Digital output value (16 bits)
Minimum Maximum Minimum Maximum
4 to 20mA
-1536 65535 -768 32767
0 to 20mA
4 to 20mA
(Extended mode)
-17536 73535 - -
User range setting
(Uni-polar)
-1536 65535 -768 32767