3 - 21 3 - 21
MELSEC-Q
3 SPECIFICATIONS
1) For input signal error detection at a level of the lower limit value only
• Input signal error detection extended setting: 1 (Different upper limit value and
lower limit value)
• Input signal error detection upper limit setting value: 251 (Input signal error
detection invalid)
• Input signal error detection lower limit setting value: 100 (10.0%)
2) For input signal error detection at a level of the upper limit value only
• Input signal error detection extended setting: 1 (Different upper limit value and
lower limit value)
• Input signal error detection upper limit setting value: 100 (10.0%)
• Input signal error detection lower limit setting value: 251 (Input signal error
detection invalid)