11 TROUBLESHOOTING
Mitsubishi Diesel Engine S16R & S16R2 OPERATION & MAINTENANCE MANUAL
200
Pub. No. K29001-00320 Revision: 1
During Normal Operation, Thermo Switch Activated
Table 11-13 During Normal Operation, Thermo Switch Activated
Problem Cause Remedies
Reference
Page
During Normal Opera-
tion, Thermo Switch Ac-
tivated
Coolant temperature
raised
Restart the engine in the following order: -
1 Operate the engine at low idle
speed to cool down
immediately.
2 Stop the engine.
3 Check the coolant level.
4 Check the ambient
temperature.
5 Bleed air from the cooling
system.
6 Check the radiator, fan, and
fan belt.
7 Check the coolant
temperature.
8 If no fault has been found,
restart the engine.
• If any fault is found, contact
your SME dealer
"CONTACT
LIST" (→ Page 8).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi S16R Series and is the answer not in the manual?

Mitsubishi S16R Series Specifications

General IconGeneral
Fuel TypeDiesel
Cooling SystemWater-cooled
Starting SystemElectric starter
Engine Type4-cycle, water-cooled, direct injection
AspirationTurbocharged, Intercooled
RotationCounter-clockwise (viewed from flywheel side)
Fuel SystemDirect injection
Lubrication SystemForced lubrication
Engine ModelS16R

Related product manuals