55
Markings, Certificates and Approvals
GB
Model 9010/9020 SIL
10 Markings, Certificates and Approvals
10.1 ATEX Directive
Response time (without detector)
for the change from 0 to 50 % FS
Analog output =< 1.0 s
WARNING relay =< 0.6 s
ALARM relay =< 0.6 s
Failure relay =< 0.7 s
Zero and span drift (without
detector)
< ±0.5 % FS. ±1 digit/month
Accuracy (without detector) ±1 % FS. ±1 digit
Ambient Conditions (including
spare parts)
Operating temperature -10 °C - +55 °C
Storage temperature -20 °C - +60 °C
Humidity max. 90 % RH non condensing
Vibration
10 - 30 Hz, amplitude 1 mm
31 - 100 Hz, max. acceleration 19,6 m/s²
Ingress Protection
IP 20 (19" rack version)
IP 65 (Wall mounted version)
Dimensions (WxHxD)
19" rack module: 41 x 129 x 220 mm
Wall Mounted Unit: 255 x 180 x 90 mm
Weight
19"rack module 450 g
Wall mounted version:1.3 kg
Communication Interface
Manufacturer:
MSA Europe GmbH
Schlüsselstr.12
CH - 8645 Rapperswil-Jona
Product: CONTROL UNIT 9010 / 9020 SIL
Standards:
EN 60079-29-1 :2007
EN 50104 :2010
EN 50271 :2010
Marking:
II (1)G Remote detector has to be connected with intrinsic
safe supply to the CONTROL UNIT 9010 / 9020 SIL
II (1)G (2)G
EU-Type Examination Certificate: BVS 16 ATEX G001 X
Quality Assurance Notification: 0158
Year of Manufacture: see Label
Serial No.: see Label
National Certification: PFG 16 G 001 X
Standards:
EN 50104:2010
EN 50271:2010