6. Connect filling pump to filling connection
(1) on suction side of filter.
7. Open vent valve (2) and fill with fuel until it
emerges from the vent pipe (3).
8. Close vent valve (2).
9. Turn slide (4) a little (approx. 30°) and
open vent valve(s) (2) until fuel emerges
from the vent pipe (3).
10. Close vent valve(s) (2).
11. Turn slide (4) back to the locked position.
MS150119/00E 2014-08 | Task Description | 87