390 – AL MCR exceeded
Yellow alarm; warning
Cause Corrective action
DBR/MCR function: MCR
(continuous maximum rate) was
exceeded.
u -
400 – AL Open Load Digital Input 1
Yellow alarm; warning
Cause Corrective action
Line disruption at digital input 1. u Check wiring (→ Page 138).
401 – AL Open Load Digital Input 2
Yellow alarm; warning
Cause Corrective action
Line disruption at digital input 2. u Check wiring (→ Page 138).
402 – AL Open Load Digital Input 3
Yellow alarm; warning
Cause Corrective action
Line disruption at digital input 3. u Check wiring (→ Page 138).
403 – AL Open Load Digital Input 4
Yellow alarm; warning
Cause Corrective action
Line disruption at digital input 4. u Check wiring (→ Page 138).
404 – AL Open Load Digital Input 5
Yellow alarm; warning
Cause Corrective action
Line disruption at digital input 5. u Check wiring (→ Page 138).
405 – AL Open Load Digital Input 6
Yellow alarm; warning
Cause Corrective action
Line disruption at digital input 6. u Check wiring (→ Page 138).
406 – AL Open Load Digital Input 7
Yellow alarm; warning
Cause Corrective action
Line disruption at digital input 7. u Check wiring (→ Page 138).
MS150094/02E 2015-05 | Troubleshooting | 65