8.19.3 Water level probe (3-in-1 rod electrode) – Check
Preconditions
System is put out of service and emptied.
WARNING
Fuels are combustible and explosive.
Risk of fire and explosion!
Avoid open flames, electrical sparks and ignition sources.
Do not smoke.
Wear protective clothing, protective gloves, and safety glasses / facial protection.
Checking water level probe (3-in-1 rod electrode)
1. Disconnect connector from water level probe.
2. Unscrew water level probe.
3. Disconnect connector from water level probe.
4. Immerse water level probe into a tank filled with water until water level reaches the thread.
5. Switch on the system.
Result: Water drain valve opens.
6. Leave water level probe in tank.
Result: Alarm must be issued after the preset time.
7. Switch off the system.
8. Disconnect connector from water level probe.
9. Remove water level electrode from tank.
10. Screw in water level electrode.
11. Disconnect connector from water level probe.
12. Fill system, vent and put into operation.
MS150060/04E 2016-02 | Fuel Supply System | 127