EasyManuals Logo

Murphy Cascade CD101 User Manual

Murphy Cascade CD101
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
Specifications
Power input: 9-35VDC continuous - operates during total blackout for 2 sec. min.
Power consumption: Sleep Mode (Manual): 1mA typical;(Automatic) 4mA typical.
Running Mode (Manual): 20mA typical; (Automatic): 24mA typical.
Operating/Storage temperature: -40 to 85°C; (-40 to 185°F).
Humidity: 0-100%, non-condensing.
Housing: UV stabilized black polycarbonate and epoxy encapsulation. Weather tight and includes sealing
gasket to keep moisture and debris out of enclosure. Properly mounted controller will maintain NEMA4 / IP65
rating of enclosure.
Vibration: Rated to 6G.
Impact: Rated to 10G.
Inputs: Dedicated digital inputs for low oil pressure, high engine temperature, remote start, DC charge
fail/Alternator fail. Two aux inputs are configurable for multiple functions.
Outputs: 7 – 4 auxiliary, configurable (1A DC protected). 3 dedicated outputs for Crank, Fuel/ECU,
Alternator excitation. Outputs are low side FET switches.
Crank attempts: 3, 5, 10, Continuous.
Crank Rest: 5-60 seconds, adjustable.
Shutdown lockout time delay: 5, 10, 15, 20, 25, 30 seconds.
Crank disconnect speed setting: Field settable 0-9999 RPM (16-60Hz AC freq input).
Overspeed/underspeed trip point setting: ±5 to 50% of nominal.
Speed sensing inputs: Magnetic pickup (5-120VAC RMS / 0-10 kHz) & AC frequency (30-600VAC RMS /
16-80 Hz).
CANbus interface: Directly reads engine speed, oil pressure, coolant temperature, system voltage, & engine
status data* from SAE-J1939 enabled engines.
MODbus interface: In J1939 applications drives PVA series analog gages. Gages limited to tach (0-3000
rpm), coolant temperature, oil pressure (0-100 & 0-150), DC volts (12v & 24v), AC freq, and audible alarm.
*Engine status data limited to low oil pressure, high engine temperature, “Wait to start” status, Warning & Fault
lamp information, and communication error.