4.3 When Stopping the Compressor for a Long Time
When stopping the compressor for a long period of time, make sure to perform the following steps:
Turn off the motor main power.
Turn off the heater power and control panel power.
Close the suction and discharge side shut-off valves.
If an economizer or liquid injection is used, close the stop valve located at the compressor inlet.
When the compressor is stopped for more than a month, perform the following steps once a month:
Turn the compressor shaft by removing the motor spacer plate (P/N: 235-2).
Measure the unit pressure.
Check for refrigerant leakage.
When restarting the compressor which has been stopped for more than a year, perform the following
steps.
Check the motor insulation resistance.
In addition, conduct the items instructed in the motor instruction manual.
Replace or analyze the lubricating oil. When analyzing, if it is found as a result of the analysis
that the control criteria given in this Chapter, Section 4.1.5 Tables 4-1 to 4-2 are not satisfied,
the oil must be replaced.
Check for refrigerant leakage.
Supply power to the oil heater at least half a day before staring operation..
Before starting the operation, confirm that the refrigerant is not condensed in the package unit
by checking the package temperature and pressure.
.
.