EasyManua.ls Logo

NAPCO StarLink SLE-LTEVI-FIRE User Manual

NAPCO StarLink SLE-LTEVI-FIRE
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
StarLink
SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 1
ADDITIONAL COMPONENTS
In addition to the SLE-LTEVI-FIRE listed above, the fol-
lowing sub-assemblies are available:
SLE-WIFI-MODULE - Allows your Napco StarLink
device
to connect to the Internet by means of a wireless (Wi-Fi)
link, eliminating a wired Ethernet cable connection.
Note: 7AH battery required when using the SLE-
WIFI-MODULE. For more information, see WI2191.
SLE-DLCBL - Download Cable, 6 feet.
SLE-ANTEXT30 - Extended antenna with 30 feet of cable
SLE-ANTEXT50 - Extended antenna with 50 feet of cable
SLE-ANTEXT75 - Extended antenna with 75 feet of cable
(Any suitable external cellular antenna is permitted by
UL). Always follow the manufacturer's installation in-
structions. Note: Antennas are not Listed by UL. For
LTE radios where an External Antenna needs to be in-
stalled outside of the room in which the radio is installed
(maximum 30 meters (98 feet) in Residential applica-
tions), please use RF Transmitter Board
9SLELTEEXAPSLD available from our Customer Ser-
vice Department, if not provided. The
9SLELTEEXAPSLD is identified by "two red dots" locat-
ed on the lower right corner of the board. See WI2239
included with the 9SLELTEEXAPSLD for the simple in-
stallation procedure.
SPECIFICATIONS
Electrical Ratings for +12V / 24V (powered by the con-
trol panel)*
 Input Voltage: 10-25VDC regulated (power-limited out-
put from Listed control panel).
 Input Current:
10VDC standby: 162mA
12VDC standby: 125mA
15VDC standby: 110mA
24VDC standby: 100mA
25VDC standby: 100mA
Wi-Fi Module: (Optional) Add 40mA to the above.
(With peak RF transmission current of 300mA).
Electrical Ratings for the IN 1 Fire Input:
 Input Voltage: 9-25VDC.
 Maximum Input Current: Up to 2mA from FACP NAC
circuit
WI2326LF 12/18
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at
http://tech.napcosecurity.com/
(Note: Technical Service is for security professionals only)
Publicly traded on NASDAQ Symbol: NSSC
© NAPCO 2018
INTRODUCTION
The SLE-LTEVI-FIRE Dual-Path Alarm Communicator is
specifically designed to interface with FACP (Fire Alarm
Control Panels) and to comply with UL 864. The SLE-
LTEVI-FIRE is equipped with two dry relays, one for a
trouble output and one for an auxiliary output. The unit is
also equipped with four supervised inputs to report a Fire
Alarm, a Fire Trouble, a Water Flow Alarm and a Supervi-
sory Alarm, each triggered from the N/O and Common ter-
minals of the associated FACP output relays.
When connected to a FACP with one or two standard RJ-
45 telephone inputs, the SLE-LTEVI-FIRE provides two
RJ-45 outputs to satisfy both telephone inputs. The prima-
ry RJ-45 output is supervised and reports a trouble to the
central station upon any open or short on the primary RJ-
45 wires that prevent reporting. The secondary telephone
line is supervised by the FACP; when a line fault is detect-
ed, a trouble is reported to the central station through the
primary telephone line.
When connected to a FACP without digital dialing capabil-
ity, the StarLink
SLE-LTEVI-FIRE Dual-Path Commercial
Fire alarm capture radio communicator is a fully super-
vised, wireless digital two-way subscriber unit supported by
an extensive nationwide wireless network. The SLE-
LTEVI-FIRE is compatible with most 12 or 24VDC alarm
control panels (always adhere to the documentation provid-
ed by the control panel manufacturer). Mount the unit to a
single-, dual-, or three-gang electrical box and route the
wires through the back knockout(s), or as specified by local
codes. See WI2140 for programming information.
The SLE-LTEVI-FIRE communicator uses proprietary
data-capture technology that captures the alarm report
from the control panel and transmits the alarm signals to
the SLE Control Center; the alarm signals are then for-
warded to ANY central station via Contact ID or 4/2 via
DACT from the NOC or Sur-Gard System II, Sur-Gard Sys-
tem V, Bosch D6100IPV6 or Bosch D6600 Receiver (with
ITS-D6686 Ethernet Adapter) via TCP/IP using standard
line security. The SLE Control Center reports a trouble
signal in the event that the network does not receive the
expected supervision signal from the wireless communica-
tor. In addition, the SLE-LTEVI-FIRE is powered directly
from the control panel.
SLE-LTEVI-FIRE - Commercial / Residential Fire LTE Veri-
zon Network Compatible GSM alarm capture Communi-
cator. SIM card included. Red plastic enclosure. Rated
nominal 12/24VDC input.
StarLink™
Commercial SLE-LTEVI-FIRE
Dual-Path Alarm Communicator
INSTALLATION INSTRUCTIONS
*For Commercial Fire installations, a UL Listed Fire Alarm regulated power
supply or FACP regulated auxiliary output is required.
AGENCY LISTINGS
 UL 864 Standard For Control Units and Accessories For
Fire Alarm Systems, 10th Edition
Question and Answer IconNeed help?

Do you have a question about the NAPCO StarLink SLE-LTEVI-FIRE and is the answer not in the manual?

NAPCO StarLink SLE-LTEVI-FIRE Specifications

General IconGeneral
NetworkLTE
Power12VDC
ModelSLE-LTEVI-FIRE
ListingUL Listed
ManufacturerNAPCO

Summary

Introduction and Components

Additional Components

Lists optional sub-assemblies like Wi-Fi modules and extended antennas.

Specifications Overview

Details electrical ratings, power requirements, and input/output specifications.

System Terminals and Wiring

Terminal Descriptions

Explains the function and wiring of various terminal blocks (TB1-TB13) and Ethernet.

Fire Input Wiring Options

Provides a wiring diagram for supervised fire input options.

LED Status Indicators

RF Signal Strength and Operational LEDs

Describes green RF signal strength and yellow operational status LEDs.

Network, Trouble, and Diagnostic LEDs

Details red trouble, diagnostic, IP network, and yellow IP state LEDs.

Installation and Configuration

Jurisdictional Notice

Lists fire programming options and their UL 864 compliance.

Supplying Power

Explains power requirements and the use of UPS for connected devices.

Jumper Descriptions

Details the function and options of jumper block "X5".

Network Coverage

Explains how the StarLink radio monitors cell network coverage.

Wiring Diagrams and Procedures

Primary Reporting Configuration

Wiring diagram for generic FACPs without TELCO RJ Sockets.

FACP Relay Trigger Input Reporting

Wiring diagram for FACP relay trigger input reporting.

GEMC Control Panel Wiring

Wiring diagram for GEMC-32, GEMC-96, GEMC-128 and GEMC-255 Control Panels.

Advanced Supervision and Compatibility

Alternate Telco Line Supervision

Method for supervising the telephone line connection to the control panel.

4/2 Pulse Dialing Format Compatibility

Lists compatible receivers and dialing formats for the SLE Series Radios.

Installation Steps and Troubleshooting

Account Registration

Steps for creating an account and registering StarLink radio modules.

Mounting Location Selection

Recommendations for selecting an optimal mounting location for RF performance.

Programming Radio Troubles

Methods for programming the control panel to annunciate StarLink radio troubles.

Warranty Information

Napco Limited Warranty

Details the manufacturer's warranty terms and conditions for products.

Related product manuals