EasyManua.ls Logo

Nastec Vasco V409 - Page 12

Default Icon
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Control board
Analog inputs (10 or 15 Vdc):
1. AN1: 4-20 mA: sensor 1
2. AN2: 4-20 mA: sensor 2
3. AN3: 4-20 mA / 0 - 10 Vdc (settable
by jumper C.C.): external set
4. AN4: 4-20 mA / 0 - 10 Vdc (settable
by C.C.): trimmer for frequency
regulation / external set 2
Digital outputs:
motor run signal:
NO1, COM1: closed contact with motor running.
NC1,COM1: closed contact with motor stopped.
alarm signal
NO2,COM2: closed contact without alarm.
NC2,COM2: closed contact with alarm or no power
supply.
DOL1 pump relay:
NO3,COM3: closed contact with DOL1 running.
NC3,COM3: opened contact with DOL1 running.
DOL2 pump relay:
NO4,COM4: closed contact with DOL2 running.
NC4,COM4: opened contact with DOL2 running.
Relays are no voltage contacts. Max. voltage to the
contacts is 250 V with max current of 5 A.
RS485 for COMBO:
S1+
S1-
G
It is recommended to
respect the polarity
linking more units in
series.
Digital inputs:
IN1 : motor start & stop
IN2: value set 1 & 2 switching
IN3: sensor 1 & 2 switching
IN4 : motor start & stop + alarms
reset
0V
We recommend using only no voltage
contacts.
Opening or closing the digital contacts
(depending on software configuration
set (see IN/OUT. parameters) you can
start or stop the motor.
RS485 for MODBUS:
S2+
S2-
G
It is recommended to
respect the polarity.