Nastec Vasco V409 - 6.6 Motor parameters

Default Icon
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
Parameter
Default
Description
Constant value
Fix speed
Const.value 2 set
Fix speed 2 val.
External speed
00
Address:
00 master
01 to 07 slaves
OFF
Function to allow alternating between
the inverters connected in COMBO (or
pumps connected in DOL) in order to
allow equal use of each pump in the
group; master will reorganize the starting
priority of the pumps by checking the life
of each of them.
0
Maximum difference in terms of hours
between units in the group.
0 stays for 5 minutes.
OFF
With this parameter it is possible to
activate the synchronous operation
(same speed) of the pumps in COMBO.
It is however necessary to appropriately
lower the parameter "f. min. control".
0
Delay time with which the slaves start
after the variable speed pump has
reached the maximum frequency and the
pressure value has fallen below set value
delta control
Direct
Direct: increasing motor speed also
misured value increases
Reverse: increasing motor speed, misured
value decreases.
0
Pump periodic autorun after XX hours of
inactivity. Value 0 makes function
disabled.
Warning, review the advice in chapter 1.
0.65
Cosphi value below which the unit stops
the motor and give “no water” alarm.
10
Restart delay after a dry running alarm.
At each tentative (max 5) restart delay
will be doubled.
6.6 Motor parameters
Parameters
Default
Description
XXX
Motor rated voltage (as shown on motor nameplate).
Address
XX
Alternance
ON/OFF
Alternance period
XX [h]
COMBO synchrony
ON/OFF
Start delay AUX
t = XX [s]
PI control
Direct/Reverse
Periodic autorun
t = XX [h]
Dry run cosphi
X.XX
Restarts delay
XX [min]
Rated motor Volt.
XXX [V]