NI 9411 Operating Instructions and Specifications 20 ni.com
Safety
Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM
or V
sup
-to-COM ................................ 30 V max,
Measurement Category I
Isolation
Channel-to-channel .................... None
Channel-to-earth ground
Continuous...........................30 V
rms
, 42.4 V
pk
, 60 VDC
Withstand .............................400 V
rms
, verified by a 5 s
dielectric withstand test
Measurement Category I is for measurements performed on
circuits not directly connected to the electrical distribution system
referred to as MAINS voltage. MAINS is a hazardous live electrical
supply system that powers equipment. This category is for
measurements of voltages from specially protected secondary
circuits. Such voltage measurements include signal levels, special
equipment, limited-energy parts of equipment, circuits powered by
regulated low-voltage sources, and electronics.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Other manuals for National Instruments NI 9411

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments NI 9411 and is the answer not in the manual?

National Instruments NI 9411 Specifications

General IconGeneral
BrandNational Instruments
ModelNI 9411
CategoryControl Unit
LanguageEnglish

Related product manuals